774(Solved): DTW-114 Fault showing. Pump locally running. Need to check.

Posted on 29th April 2024, 2:02pm by [email protected]

2024-06-04 02:40:29pm: Status changed to Solved, Because of: work done. -by: Parves

No Attachment Found
...
Parves,Automation Technician on 16th May 2024, 8:04am

SCADAPack program problem.

...
Parves,Automation Technician on 02nd June 2024, 11:00am

02.06.2024: Today I check why DTW-114 is unable to operate remotely. I check Modbus serial communication from Generato, GiMAC & VFD control drive. I found VFD control drive's Modbus SL port can't communicate with SCADAPack. Need to change the Controller.

...
Parves,Automation Technician on 04th June 2024, 2:40pm

VFD controller drive change. Now this DTW is remotely operational.