791(Solved): IRP-02 Sand filter E-L all system not working... Need to emergency check...
2024-05-21 12:35:35pm: Status changed to Solved, Because of: Optical connection isn't found between Fiber converter module (FCP-301 to FCP-302)
We maintenance the fiber in FDF patch cord terminal box.
And cable arrangement was
Cable Route:
PC-1, FC-blue, Cable-2
PC-2, FC-Orange, Cable-2
PC-3, FC-green, Cable-2
PC-4, FC-Red, Cable-2
PC-5, FC-blue, Cable-1
PC-6, FC-orange, Cable-1
PC-7, FC-green, Cable-1
PC-8, FC-Red, Cable-1 -by: Parves