878(Solved): DTW-207 Inverter (VFD) fault problem. Need to check by ICE team.

Posted on 12th June 2024, 9:25am by [email protected]

2024-06-16 02:56:34pm: Status changed to Solved, Because of: Motor short ckt problem shows in HMI. Dismental the VFD electronic parts & found the roof of problem & solve it. -by: Parves

No Attachment Found
...
Md. Ruhul Amin,SCADA Operation Engineer on 12th June 2024, 11:18am

Inspections: 1. Input Voltage check- ok 2. DC bus voltage check- ok 3. Motor Coil resistance check- ok 4. Coil to Ground Short ckt check- ok