WID1656: DTW-222, Camera No. 66, View not showing in monitor. Need to check.
WID1655: DTW-221, Camera No. 61, View not showing in monitor. Need to check.
WID1654: DTW-221, Camera No. 60, View not showing in monitor. Need to check.
2025-March(03)-12(Wednesday)
WID1627: DTW-112 VFD HMI display value not showing. Need to check....
2025-March(03)-11(Tuesday)
WID1626: DTW-123 Camera no. 189
ব্রেক ডাউন এর জন্য ক্যামেরার ক্যাবল খুলের রাখা প্রয়োজন।
2025-March(03)-10(Monday)
WID1625: SCADA Server room AC-04 Maitenance Servicing & Gas Charge
WID1624: SCADA Server room AC-03 Maitenance Servicing & Gas Charge
WID1623: SCADA room AC-02 Maitenance Servicing & Gas Charge
2025-March(03)-09(Sunday)
WID1621: Dtw 123 ground short circuit fault coming. Need to check
WID1620: Sand filter H (3V07H) অটোমেটিক রিমোট থেকে লোকাল হয়ে যায়
WID1619: Irp2 Backwash Holding Tank A Automatically From REM To LOCAL Mood is showing.
Need to check.
2025-March(03)-08(Saturday)
WID1618: IRP-02 Sand filter F Mov-3V07F display not showing. SCADA Fault showing. Need to check.
WID1617: DTW-205 Nothing is visible on the VFD HMI display.But SCADA display value showing. (Pump locally running for IRP-02 FCP panel problem purpose.)
WID1616: Irp-2 sand filter এর FCB panel (B,C ) পাওয়ার চলে গেছে।
2025-March(03)-05(Wednesday)
WID1615: 575001185004763 UPS repair.
WID1614: Dtw 219 communication error.
2025-March(03)-01(Saturday)
WID1613: Dtw 103 Radio communication error. Need to check
WID1612: Dtw 216 UVR trip. Need to check
WID1611: DTW205 CCTV UPS Problem
2025-February(02)-27(Thursday)
WID1610: DTW104 Camera 120 view not showing in monitor. need to chack.
WID1609: DTW104 Camera 119 view not showing in monitor. need to chack.
WID1608: DTW104 Camera 118 view not showing in monitor. need to chack.
2025-February(02)-26(Wednesday)
WID1605: DTW-203 লোকাল/রিমোট কোন মোডেই run হচ্ছে না। Need to check.
WID1604: DTW-203 Communication feedback very very slow. Need to check.
2025-February(02)-25(Tuesday)
WID1603: DTW-207 FIT problem. Need to check.
WID1602: DTW-201 FIT problem. Need to check.
2025-February(02)-22(Saturday)
WID1601: DTW-208 Communication feedback very slow. Need to check.
2025-February(02)-20(Thursday)
WID1600: DTW-204 Communication feedback very slow. Need to check.
WID1598: DTW-G-Mac value not showing. Need to check...
WID1597: DTW-121 Communication problem. Pump locally running.. Need to check...
2025-February(02)-19(Wednesday)
WID1599: DTW-222 Communication feedback very slow. Need to check.
WID1595: DTW-119 Communication feedback very slow. Need to check.
WID1594: DTW-120 Communication feedback very slow. Need to check.
2025-February(02)-18(Tuesday)
WID1587: DTW-115 ACB close command not accepted.Need to check.
WID1586: Dtw 107 communication problem .need to check
WID1585: Dtw 103 local network line EPRV MOV not controlling by scada
2025-February(02)-17(Monday)
WID1583: Dtw-113 VFD Programme setting check.
WID1582: Dtw 106 communication error. Locally running. Need to check
2025-February(02)-14(Friday)
WID1581: Scada Operational 1 no. Pc Automatically run and stop. Need to check ice team.
2025-February(02)-11(Tuesday)
WID1579: Dtw 116 scada system have been stuck need to check
WID1578: Office building 2nd floor internet switch power supply cable integration with the backup power line
2025-February(02)-10(Monday)
WID1577: DTW-104 LIT Problem. Need to check...
2025-February(02)-08(Saturday)
WID1576: DTW-208 Start/Stop problem. Need to check...
2025-February(02)-05(Wednesday)
WID1575: Dtw-217 PIT Problem. Need to check ice team.
WID1574: Dtw-115 PIT Problem. Need to check ice team.
WID1573: Dtw-113 PIT Problem. Need to check ice team.
2025-February(02)-04(Tuesday)
WID1538: Dtw 123 pump panel main magnetic contact not working
WID1537: DTW-116 Camera ID-14 View now showing in monitor.
WID1536: DTW-116 Camera ID-13 View now showing in monitor.
2025-February(02)-03(Monday)
WID1527: Irp-1 sand filter 'L' LIT wrong value showing. Need to check
WID1526: DTW-104 FIT problem. Flow not showing in SCADA. Need to check.
WID1517: DTW103 CCTV Camera cable tagging and pillar marking
2025-February(02)-02(Sunday)
WID1514: Lighting Arrester Installation at dtw-222
WID1513: Lighting Arrester Installation at dtw-212
2025-February(02)-01(Saturday)
WID1512: Lighting Arrester Installation at dtw-201
WID1511: Lighting Arrester Installation at dtw-209
WID1510: Lighting Arrester Installation at dtw-205
2025-January(01)-30(Thursday)
WID1497: DTW-221 LIT problem. Need to check.
2025-January(01)-29(Wednesday)
WID1509: Lightning Arrester installation at dtw-117
WID1508: Lighting arrester installation at dtw-109
WID1507: Lighting arrester installation at dtw-105
2025-January(01)-28(Tuesday)
WID1503: DTW NO 118 CAMERA NO 166 VIEW NOT SHOWING IN MONITOR.NEED TO CHACK.
WID1502: DTW NO 118 CAMERA NO 165 VIEW NOT SHOWING IN MONITOR.NEED TO CHACK.
WID1501: DTW NO 118 CAMERA NO 164 VIEW NOT SHOWING IN MONITOR.NEED TO CHACK.
2025-January(01)-27(Monday)
WID816: DTW-218 Communication and SCADApac problem. Need to check.
2025-January(01)-26(Sunday)
WID1491: DTW-121 TO 123 CCTV Optical fiber Maintenance.
WID1490: DTW-116 Camera ID-14 View now showing in monitor.
WID1489: DTW-116 Camera ID-13 View now showing in monitor.
2025-January(01)-25(Saturday)
WID1483: Dtw 110 camera no:132 alignment need to adjust
WID1482: DTW-217 FIT problem. Need to check.
WID1481: DTW-208 FIT problem. Need to check.
2025-January(01)-23(Thursday)
WID1480: The optical fiber has cut between 104 and 103. Need to check ice team.
785: Dtw 208 VFD fault is showing. Field check problem not solved.
Need to check
2024-May(05)-06(Monday)
784: DTW-211 PIT value isn't show in SCADA. Need to check.
2024-May(05)-04(Saturday)
779: HP Laser Jet 700 M712 printer ink installation.
778: HP Color Laser Jet CP6015n printer ink installation.
777: DTW-215 has VFD problem. Need to check emergency.
2024-May(05)-01(Wednesday)
775: Irp1 all pump can't accept pump run command.
Need to check urgently.
Evening time after scada maintenance work time scada operation work going to slow mood.
Need to check urgently
2024-April(04)-30(Tuesday)
774: DTW-114 Fault showing. Pump locally running. Need to check.
773: IRP-02 Backwash holding tank level valve not showing. Need to check.
2024-April(04)-29(Monday)
772: DTW-103 Communication problem. Need to check.
2024-April(04)-28(Sunday)
771: Intercom Power not showing display off . Need to check...
770: Dtw 104 VFD fault. The pump is locally running. Need to be check
2024-April(04)-24(Wednesday)
769: Dtw 114 Local Pipe line MOV -01 automatic close when MOV-01 turn in Remote mode, Need to check
2024-April(04)-23(Tuesday)
765: All tag entry to the cmms software
698: Dtw-122 & 123 optical fiber problem check & maintenance.
2024-April(04)-22(Monday)
759: IRP-01 SCADA Server room east side AC drain water is enter to the sever room. The room is flooded by the water. Need to repair early.
750: IRP2 Server UPS individual battery voltage check for the battery health status
2024-April(04)-21(Sunday)
764: Instrument integration control and maintenance station room AC maintenance
760: IRP-02 Electric Panel room right side AC is not functional. Need to repair immediately.
758: 47 No's PoE Switch check & Maintenance.
2024-April(04)-20(Saturday)
756: CC Camera Installation at IRP-01 Electrical panel room.
755: IRP-01 SCADA Room 56'' three monitor up for both IRP-01 & IRP-02, Two for IRP-01 and Two for IRP-02.
2024-April(04)-18(Thursday)
754: IRP-02, Plant inside CC Camera integration at IRP-01 SCADA room.
752: DTW-204 LIT level suddenly down. Need to check.
2024-April(04)-17(Wednesday)
783: Terminal box installation for FIT at 45 no DTW
2024-April(04)-08(Monday)
745: DTW-210
PWP Panel & VFD installation.
2024-April(04)-02(Tuesday)
740: Dtw 201 VFD fault showing.need to check
2023-November(11)-02(Thursday)
551: FIT-3001,3002,2001,4001,4002,4004 signal efficiency check & maintenance planning.
2023-October(10)-12(Thursday)
538: Dtw 205 radio communication totally error.need to check emergency.now it's locally running.
536: Dtw 117 mov-2 fault showing.need to check
2023-October(10)-01(Sunday)
520: DTW-204 Flow not showing in SCADA. Need to check...
2023-August(08)-31(Thursday)
481: Lab room internet connection.
2023-August(08)-30(Wednesday)
476: DTW-207 CCTV optical fibre maintenance.
2023-August(08)-29(Tuesday)
475: IRP-01 & IRP-02 all CCTV panel, equipments clean.
2023-August(08)-07(Monday)
432: Irp2 sand filter bed E LIT problem. Need to be checked.
418: Dtw-114 - 119 CCTV view not Showing in scada. Need to check ICE Team.
2023-August(08)-06(Sunday)
431: DTW-211 ACB Button not working. Need to check.
430: DTW-110 LIT Problem. Need to check.
2023-August(08)-02(Wednesday)
426: DTW 113 replacement with general PLC by Sincos.
2023-July(07)-25(Tuesday)
413: DTW-216 PIT Problem. Need to check.
407: IRP-2 SANDFILTER ALL FCP & LOP PANEL CLEANING.
406: DTW-201,219 PIT PROBLEM NEED TO CHECK.
2023-July(07)-24(Monday)
410: DTW-114 VFD Problem. Need to check.
409: DTW-215 GMAC KW not showing in SCADA.
2023-July(07)-19(Wednesday)
399: Dtw-101, Stop Command not accept in Scada.
372: DTW-203, 204, 206, 208 Communication Error. Need to check.
369: DTW-115 ACB SCADA command not accept. Need to check.
2023-July(07)-15(Saturday)
397: DTW radio antenna RSSI check need G4S co-operation IRP1 and IRP2 area all DTW.
2023-July(07)-13(Thursday)
396: DTW-215 PLC-221 Replacement work.
2023-July(07)-12(Wednesday)
379: Irp-2 back wash holding tank-A pump '3P01A' manual mode to auto mode not changing.
2023-July(07)-06(Thursday)
386: Dtw 211 PIT And FIT both are problem. FIT Not good conditions. Need to be check.
384: WO384: Dtw 104 Scada run Command not accepted. Now locally running.
Need to check
2023-June(06)-26(Monday)
378: Dtw 116 VFD fault showing.need to check
2023-June(06)-22(Thursday)
374: Dtw 218 RTU panel SPT Problem, Need to be check.
371: DTW-221 SCADA Command do not accept. Pump locally running. Need to check.
370: DTW-202 Automatically start/stop problem. Need to check....
2023-June(06)-21(Wednesday)
373: Optical Fiber cable isolate from the pole in front of Chairs Bridge .
(IRP#1 and IRP#2 Fiber comm. Cable)
2023-June(06)-20(Tuesday)
368: SPD check and installation IRP1 and IRP2 area all DTW.
363: Dtw 106 Flow Value not showing. Need to check.
2023-June(06)-19(Monday)
366: Dtw-205, ACB runs, but when everything is normal after giving control source to PWP panel everything shut down. At present the pump has ACB run. Everything else is kept local. Need to check (Emergency) morning time.
312: DTW- 122,123 AND 204 Radio Communication Error.
2023-June(06)-12(Monday)
360: DTW106 PIT problem need to check.
2023-June(06)-08(Thursday)
262: DTW- 201,214 ,122,123 Radio Communication Error
261: DTW115, DTW117, DTW118, DTW119 Radio Communication
Problem not solved yet. Need To Check Again. Right Now, We Can't run these pumps from the SCADA.
355: DTW214 LIT,PIT,FIT isolation for regeneration purpose.
353: Dtw-201,203,208 Optical Fiber restoration.
2023-June(06)-04(Sunday)
354: Laboratory network (internet) problem. Need to check.
326: Optical fibre torn at DTW214 and DTW121
321: DTW-118 Long time communication erorr
2023-June(06)-03(Saturday)
350: Chlorine PLC panel new isolator installation.
349: Irp2 Has no SCADA system. Need a Scada system at irp2 scada room.
348: Irp1 and Irp2 Total 25+25 = 50 Cc camera deactivated. Urgently Need to check.
2023-May(05)-30(Tuesday)
347: DTW-221 Automatically start/stop problem. It could be serial communication problem. Need to check.
344: 102, 217, 219, 221 FIT Value not showing in SCADA. Need to check.
343: DTW-219, 221 LIT Value not showing in SCADA.Need to check.
2023-May(05)-29(Monday)
342: DTW-218, 219, 220, 221, POT Value not showing in SCADA. 203 PIT field and SCADA value not same. Also SCADA PIT valve suddenly goes to high and pump automatically stop.
Need to check.
2023-May(05)-28(Sunday)
334: Calibration Of FIT- 2001, 3001 (IRP#02)
2023-May(05)-27(Saturday)
340: Dtw-214 Locally running for long time because of radio communication error.
339: IRP2 and IRP2 PWP panel thermal sensor functionality check
295: Server Rack(12U) installation at IRP1 DTW area (Total 22 DTWs)
2023-May(05)-25(Thursday)
331: IRP-01 plant inside 3 camera not showing... Need to check.
314: IRP#1 Area DTW CCTV Need TO Clean
-0001-November(11)-30(Tuesday)
736: DTW-208 Flow meter wrong value showing...
Need to check.
732: Between Dtw 214 & 215 CCTV cables are torn at various places
729: Dtw 116 Scada command not accepted. Now it's locally running need to check